The VX-3008F is a device designed to control the Voice evacuation announcements of TOA's VX-3000 Series rack-mount type voice evacuation system which is compliant with the European Standard EN54 for fire alarm systems. It has audio input terminals and can output the amplified audio signals to the speaker lines when the optional power amplifier modules are mounted.
It is possible to make an Emergency Warning Broadcast assigned a higher priority than the Emergency broadcast. Two patterns of the Emergency broadcast can be activated simultaneously. Compatible with network, the system can be configured in distributed arrangement. Features include the following functions: Digital signal processing function that enables appropriate acoustic adjustment for individual input sound sources and output amplifiers, Feedback suppressor function that automatically suppresses acoustic feedback when it occurs, VOX function that allows start/stop control of broadcast by way of an audio trigger, and ANC function that enables an ambient noise control. (The ANC function distinguishes between the unit's output sound and the ambient noise. The unit's output sound is not detected as noise.)
Indicators that show such statuses as fault status and power amplifier signal status are provided. It has 8 speaker output channels. A total of 3 power amplifier modules (2 for zone amplifier use and 1 for standby amplifier use) can be mounted. Equipped with a matrix output, the VX-3008F can be used as 2-bus speaker selector using 2 power amplifiers. Setting the matrix output destination makes 1-bus and 2-bus zones coexist. Zones can be expanded by connecting the unit having amplifier module(s) and the one having no amplifier module. As the VX-3008F is equipped with Standby amplifier input/output terminal, the standby amplifier, when mounted, can be shared among VX-3000F units.

  • Do 3 wzmacniaczy (8 przełączalnych stref pomiędzy 2 wzmacniaczami + wzmacniacz rezerwowy lub 8 adresowalnych dowolnie stref do 1 lub 2 wzmacniaczy)
  • Diody sygnalizacyjne wymagane normą EN54-16
  • Diody stanu linii głośnikowych
  • Dioda stanu awarii i wykrycia błędu
  • Procesor DSP dla sygnałów wejściowych: przestrajalne fi ltry oraz kompresor
  • Procesor DSP dla sygnałów wyjściowych: przestrajalne fi ltry, kompresor oraz opóźnienie do 2.7 sekundy




  • Specyfikacje
  • Przykład aplikacji:
  • Opis
  • Pobierz
Specyfikacje
Specyfikacje produktu:
VX-3008F VX-3004F VX-3016F
Zasilanie

31 V DC (zakres pracy: 20 – 40 V DC)

31 V DC (zakres pracy: 20 – 40 V DC)

31 V DC (zakres pracy: 20 – 40 V DC)

Pasmo przenoszenia

40 Hz - 20 kHz (±1 dB)

40 Hz - 20 kHz (±1 dB)

40 Hz - 20 kHz (±1 dB)

Zniekształcenia

< 1 % (przy 1 kHz)

< 1 % (przy 1 kHz)

< 1 % (przy 1 kHz)

Pobór mocy

max. 85 W at 31 VDC

max. 85 W at 31 VDC

max. 90 W at 31 VDC

Stosunek sygnał/szum

60 dB (or more)

60 dB (or more)

60 dB (or more)

Wejścia sterujące

16 + 2 (SAP)

16 + 2 (SAP)

16 + 2 (SAP)

Wyjścia sterujące

8 + 3 (CPU OFF), Wyjście sterujące ATT: 8

8 + 3 (CPU OFF), Wyjście sterujące ATT: 8

8 + 3 (CPU OFF), Wyjście sterujące ATT: 16

Wejście / wyjście

Wyjścia głośnikowe: 8
Wejście audio: 4 (Liniowe: -20 dBV / Mikrofonowe: -60 dBV, zasilanie Phantom)

Wyjścia głośnikowe: 4 strefy AB
Wejście audio: 4 (Liniowe: -20 dBV / Mikrofonowe: -60 dBV, zasilanie Phantom)

Wyjścia głośnikowe: 16
Wejście audio: 4 (Liniowe: -20 dBV / Mikrofonowe: -60 dBV, zasilanie Phantom)

Wskaźnik

power, run, CPU off, LAN status, RM status
emergency status faults: general, network, EMG microphone, fuse, power, CPU, zones
amplifier status: signal, peak, operate, power

power, run, CPU off, LAN status, RM status
emergency status faults: general, network, EMG microphone, fuse, power, CPU, zones
amplifier status: signal, peak, operate, power

power, run, CPU off, LAN status, RM status
emergency status faults: general, network, EMG microphone, fuse, power, CPU, zones
amplifier status: signal, peak, operate, power

Złącze

RJ45: control inputs x 2, control outputs (open collector) x 2, DS link x 1, remote microphones x 2, LAN x 2, analog link x 2

Removable screw terminals: control outputs (relay), zone outputs, standby amplifier bus, extension links, power input, audio inputs

RJ45: control inputs x 2, control outputs (open collector) x 2, DS link x 1, remote microphones x 2, LAN x 2, analog link x 2

Removable screw terminals: control outputs (relay), zone outputs, standby amplifier bus, power input, audio inputs

RJ45: control inputs x 2, control outputs (open collector) x 2, DS link x 1, remote microphones x 2, LAN x 2, analog link x 2

Removable screw terminals: control outputs (relay), zone outputs, standby amplifier bus, extension links, power input, audio inputs

Zakres wilgotności względnej pracy

90% or less

90% or less

90% or less

Zakres temperatury pracy

-5°C do +45°C

-5°C do +45°C

-5°C do +45°C

Wykonanie

-

-

-

Waga

7,9 kg

7,6 kg

7,9 kg

Akcesoria (w zestawie)

Oprogramowanie sterujące x 1, wypinane złącze (2pin) x 6, wypinane złącze (4-pin) x 1, wypinane złącze (6-pin) x 2, wypinane złącze (12-pin) x 2, wypinane złącze (17-pin) x 1, ferrytowy uchwyt na kabel x 2

Oprogramowanie sterujące x 1, wypinane złącze (2pin) x 2, wypinane złącze (4-pin) x 1, wypinane złącze (6-pin) x 2, wypinane złącze (12-pin) x 2, wypinane złącze (17-pin) x 1, ferrytowy uchwyt na kabel x 2

Oprogramowanie sterujące x 1, wypinane złącze (2pin) x 4, wypinane złącze (4-pin) x 1, wypinane złącze (6-pin) x 2, wypinane złącze (12-pin) x 4, wypinane złącze (17-pin) x 2, ferrytowy uchwyt na kabel x 2